Product details
Model Number: KD-02-01-#0497
Key Specifications/Special Features:
SpecificationsAir-insulated typeThe environmental protection materialsIP ratings up to IP54System introductionWind power busbar (here after refers to busduct) is applied for wind power unit with 750kW or above generation capabilityAir-insulated typeEnvironmental protection index of original materials can meet the requirements of RoHS Directive-compliant
IP ratings up to IP54
Product usage life is over 40 years
Tightening bolt with low temperature resistant alloy material
Rated voltage: 690V Insulation voltage: 1000V
Better performance price ratio than wind power
Wind Type | 1.5/2mW double feeder wind power unit | ||
Busduct Type | WLK | WLH | |
Standard | IEC60439-1, 2:GB7251.1, 2 | ||
Environmental Temperature | -40 to +50°C | ||
IP Ratings | IP31, IP40, IP54 (optional) | ||
Rated Insulation voltage (AC,V) | 1000/1500 | ||
Rated working voltage (AC,V) | 690/1000 | 690/1000 | |
Rated Working Current (A) | 1300, 1400, 1800, 2000(optional) | 500, 630, 800(optional) | |
Rated Peak Tolerance Current (kV) | 105 to 176 | 63 to 85 | |
Rated Short-term Tolerance Current (kV) | 50 to 80 | 30 to 40 | |
Rated Frequency(Hz) | 50 to 60 | ||
Air clearance | Between energized conductors | ≥20 | ≥20 |
Between energized conductor and enclosure | ≥18 | ≥18 | |
Cree page distance | Between energized conductors | ≥25 | ≥25 |
Between energized conductor and enclosure | ≥22 | ≥22 | |
The high-point of temperature riseon connections of busbar (K) | 70 | 70 | |
The high-point of temperature rise on tangible enclosures and covers (K) | 30 | 30 | |
Material group | Two | ||
Overvoltage categories | Four | ||
Pollution degree | Three | ||
Protect Type | First | ||
Wire | L1+L2+L3+pen | ||
Dielectric Strength(V/min) | 3750/AC, 1min | ||
Insulation Resistance (MΩ) | ≥20(phase-to-phase or phase-to-ground, 1000mΩ) |
Main Export Markets:
- Asia
- Eastern Europe
- Mid East/Africa